Pwrbkmdle3 Semi-Conductors Electronic Parts

Powerblock Modules

3 PHASE BRIDGE MODULES

IO per Device 30A75A100A
Circuit NumberNTE No.NTE No.NTE No.NTE No.NTE No.NTE No.
5574057415742574357445745
VRRM800V1600V800V1600V800V1600V
VF (Max)1.10V @ 30A1.30V @ 30A1.15V @ 75A1.15V @ 75A1.15V @ 100A1.15V @ 100A
TJ-40°C to +150°C-40°C to +150°C-40°C to +150°C-40°C to +150°C-40°C to +150°C-40°C to +150°C
ITSM (1 Cycle, 50Hz)365A270A1000A1000A1200A1200A
RthJC1.0°C/W0.42°C/W0.3°C/W0.3°C/W0.22°C/W0.22°C/W
Diag. No.619
620
618618618618

Circuit 5

Schematic Diagram

Diag. 618Diag. 619Diag. 620

POWERBLOCK NOTES:

MOUNTING:
Careful mounting of powerblocks on the heatsink is one of the most important requirements of reliable satisfactory application. The contact surfaces of powerblock and heatsink must be clean, free from contamination and damage. Finish and flatness of heatsink contact surface should be310mm. A thin and uniform film of interface thermal compound should be applied to contact surface of powerblock and heatsink. Fixing bolts have to be uniformly tightened with the specified mounting torque. Cross sections of busbars or cables have to be dimensioned so that heating up the powerblock will be avoided. This applies in particular for series connected fuses.

MAINTENANCE:
Powerblocks are maintenance-free. The assembly group should, however, be cleaned from time to time to ensure the insulation capability, the heat dissipation and thus the availability of the power converter.

WARNING:
Beryllium oxide is used in the powerblock assembly for insulation. Do not destroy the powerblock case because the beryllium oxide dust resulting from such action is hazardous if inhaled.