R61 Semi-Conductors Electronic Parts

Features
  • 16 Time Ranges in a Single Timer
  • User Sets Time Ranges (No Math - Just Flip Switches
  • Instructions right on Unit
  • Fine Tune Knob for Precision Timing
  • Pin for Pin Interchangable with Timers in the Field - No Rewiring
  • AC or DC Operation
  • CMOS Digital Circuitry - 0.5% Repeatable Accuracy
  • R61 SeriesUL CSA logo

    Programmable, DPDT, 10 Amp, AC or
    DC, Delay on Release Time Delay Relay
    Photo of R61 Series Relay
    DELAY ON RELEASE - Input voltage must be applied continuously to operate the internal relay. When the control switch is closed, the relay energizes. When the control switch is opened, timing begins. When timing is complete, the relay will de-energize. Time may be reset to zero during timing by closing the control switch.
    DPDT, 2 Form "C"
    AC or DC OPERATED
    NTE Type No.Nom.
    Volt.
    Contact
    Arr.
    Input
    Cur.
    Nom.
    Max.
    Contact
    Cur, @
    28VDC
    or
    120VAC
    Diag.
    No.
    R61-11AD10-1212VAC/DCDPDT167mA10AD36
    R61-11AD10-2424VAC/DCDPDT83mA10AD36
    R61-11AD10-120120VAC/DCDPDT17mA10AD36

    ACCESSORIES
    Mounting StylesDescriptionNTE Type No.
    Surface Mount11-Pin OctalR95-104
    Panel Mount11-Pin OctalR95-119
    DIN Rail Mount11-Pin OctalR95-114
    11-Pin OctalR95-182

      
    Dimensional DrawingTiming Range Chart
    D36

    Electrical Specifications

    Contact
    Rating: 10 Amps 240VAC or less, 1/3 HP, 240VAC or 120VAC,
    Pilot Duty 345VA, 120VAC or 240VAC, 50/60Hz
    Life: 500,000 operations at full load
    Mechanical Life: 7,000,000 operations at no load

    Input
    Nominal Input Voltages: See Chart
    Steady State Input Current: See Chart

    Timing
    Timing Adjustment Modes Available: See Timing Range Chart

    Repeat Accuracy
    ±0.5% - after established at steady temperature (4 hours)
    Timing Tolerance at High End of Range: -0, +10%
    Timing Tolerance at Low End of Range: +0, -50%
    Reset Time: 60mS Typ

    Protection
    Transient: Surge Test 10,000V for 20mS
    Dielectric Breakdown:
                 Coil To Contact: 1850 VAC
                 Across Open Contact: 1850 VAC

    Environmental Characteristics
    Operating: -20°C to +55°C

    Weight
    Std: 4.5 ozs. (130 grams) - approx

     Home Back



    Contact Us:

    Centerpointe Electronics
    5241 Lincoln Ave. Unit #A-7
    Cypress, CA 90630
    Call Toll Free: 800-272-2737
    Fax Toll Free: 800-493-7862
    Intl. Call No: 714-821-1100
    Intl. Fax No.: 714-828-0282