Operation Voltage Monitor Relays provide protection to equipment where an over or under voltage condition is potentially damaging. They monitor either AC single phase (50-400Hz) or DC voltages. No supply (input) voltage is required.The pick-up voltage setting is user-adjustable from 85-115% of the nominal voltage rating. As standard, the drop-out voltage setting is fixed at 3% below the pick-up voltage setting. The relay is energized when the monitored voltage is above the pick-up setting. The relay de-energizes when the monitored voltage is below the drop-out setting. |
AC OPERATED | NTE Type No. | Nom. Volt. | Contact Arr. | Pick-Up Voltage Range | Drop-Out Voltage Range * | Max. Contact Cur, @ 30VDC or 240VAC | R67-11A10-24 | 24VAC | DPDT | 21-27V | 20-26V | 10A | R67-11A10-120 | 120VAC | DPDT | 102-138V | 99-135V | 10A | DC OPERATED | NTE Type No. | Nom. Volt. | Contact Arr. | Pick-Up Voltage Range | Drop-Out Voltage Range * | Max. Contact Cur, @ 30VDC or 240VAC | R67-11D10-24 | 24VDC | DPDT | 21-27V | 20-26V | 10A | * Fixed at 3% below the pick-up setting.ACCESSORIES | Mounting Styles | Description | NTE Type No. | Surface Mount | 8-Pin Octal | R95-101 | Panel Mount | 8-Pin Octal | R95-118 | DIN Rail Mount | 8-Pin Octal | R95-113 |
| | Dimensional Drawing
DPDT, 2 Form "C" 
Electrical Specifications Contact Rating: 10 Amps resistive at 240VAC, 1/2 HP at 240VAC, 10 Amps resistive at 30VDC Life: 500,000 operations at full load Mechanical Life: 7,000,000 operations at no load Operational Characteristics Voltage Settings: Pick-Up: Adjustable from 85-115% of nom. Drop-Out: Fixed at 3% below pick-up setting Setting Accuracy: +0%, -5% min; +5%, -0% max Timing Values: Operate Time: 50mS Release Time: 50mS Power Required: 3VA Protection Transient: 10,000V for 20µs Indicator LED: Red LED on when relay is energized Reset: Automatic Environmental Characteristics Operating: -28°C to +65°C Note: UL Recognition Pending. |